ALP2101 (Intelligent intrinsically safe positioner 4-20mA control with 4-20mA feedback)

The main technical parameters


1. Input signal range: 4~20mA; split range 4~12mA, 12~20mA.


2. Range of feedback signal: 4~20mA; split range 4~12mA, 12~20mA.


3. Equivalent resistance: 425Ω (625Ω; HART protocol type)


4. Control precision: 0.5%


5. Linearity: 1%


6. Sensitivity: self-adaptive; or artificially set during this period from 0. 1% to 5%


7. Air supply pressure range: 0.14~0.55MPa


8. Air consumption: static air consumption ≤50NL/h; dynamic non-assessment


9. Environmental conditions: temperature -25~+60℃; humidity ≤90%


10. Vibration resistance: ≤2g (5~200HZ)


11. Intrinsic safety parameters: Ui = 28VDC; Ii = 93 mA; Pi = 0.65W; Ci = 1nF; Li = 0.2mH;


12. Storage conditions: temperature -40~+85℃; humidity ≤95%


13. Protection level: IP65


two. Programmable parameters


1. Input starting point range: 4~12mA


2. Input end point range: 12~20mA


3. Input signal: direction can be changed


4. Output signal: direction can be changed


5. Shut-off limit: starting point 0~10% end point 90%~110%


6. Travel adjustment: starting point 0~30% end point 70%~100%


7. Travel time: 0~200S


8. Output characteristics: linear, 1:25, 1:50 optional


9. Tolerance band: 0.1%~10% adjustable


10. PID parameters: adjustable


3. The security parameters are as follows:


Input circuit (terminal ± IN)


Ui = 28V, li = 93mA


Pi = 0.66W, Ci = 1 nF, Li = 0.2 mH


Output circuit (terminal ± OUT)


Ui = 28V, li = 93 mA


Pi = 0.66W, Ci = 1nF, Li = 0.2 mH


The connection between this product and the intrinsically safe end of the safety barrier should be a shielded cable with a cross-section> 0.5mm2, and the shielding layer must be grounded. The distributed capacitance and inductance of the cable must be less than the safe value. The safety barrier is installed in a safe place, and its installation and use must comply with the safety barrier instruction manual. The user is not allowed to change the electrical components in the product at will.

Previous : Model: ALP2102 (intelligent intrinsically safe positioner with HART communication protocol without 4-20mA feedback)

Next : Model: ALP2100 (Intelligent intrinsically safe positioner 4-20mA control without 4-20mA feedback)

CONTACT US
FOLLOW US
NAVIGATION
TEL. +44(0)20 31299469
FAX. +44(0)20 31291964
E-mail. sales@aerlp.co.uk
Copyright © 2021,aerlp controls Ltd.
Aerlp Controls Ltd.
14 Neasham Road,Middleton SaintGeorge,Darlington
Powered by Feedback Manage